• Inventory
  • Products
  • Technical Information
  • Circuit Diagram
  • Data Sheet
Data Sheet
Home > Data Sheet > P0300SD
P0300SD

P0300SD

Model P0300SD
Description solid state crowbar devices
PDF file Total 212 pages (File size: 2M)
Chip Manufacturer TECCOR
ITU-T K.20 and K.21
Table 4.10
K.20 Lightning Test Conditions for Telecom Equipment in Central Office/Remote Terminal
Voltage (10x700 µs)
Single Port
Metallic and
Longitudinal
Basic/Enhanced
1 kV/1.5 kV
4 kV/4 kV
Multiple Ports
Longitudinal Only
Basic/Enhanced
Current (5x310 µs)
Basic/Enhanced
(A)
25/37.5
100/100
Repetitions *
±5
±5
±5
±5
Primary Protection
None **
Installed if used
None
Installed if used
Acceptance
Criteria
A
A
A
A
1.5 kV/1.5 kV
4 kV/6 kV
37.5/37.5
100/150
* One-minute rest between repetitions
** This test is not conducted if primary protection is used.
25
Surge
Generator
Decoupling
Elements
Equipment Under Test
A
B
a) Transversal test
E
25
Surge
Generator
R
3
= 25
b) Longitudinal test
Figure 4.3
Connection Appearances
Equipment Under Test
A
Decoupling
Elements
B
E
© 2002 Teccor Electronics
SIDACtor
®
Data Book and Design Guide
4 - 11
http://www.teccor.com
+1 972-580-7777
Regulatory
Requirements
Go Upload

* Only PDF files are allowed for upload

* Enter up to 200 characters.